The Ashcroft® RXLdp differential pressure transmitter utilizes patented Si-Glas™ technology, assuring precise measurement and control at extremely low differential pressures. The unit is virtually unaffected by shock or vibration and is an ideal selection when reliable low pressure measurement is needed.
Unit of Measure

Specifications

Brands

N/A Ashcroft®

Reference Temperature

N/A 70 ºF21 ºC

Reference Temperature Tolerance (±)

N/A 2 ºF1 ºC

Accuracy

N/A ± 1.00% of Span (Terminal Point Method: Includes Non-linearity, Hysteresis, Non-Repeatability, Zero Offset and Span Setting Errors)

Stability

N/A ± 0.5% Span/Year at Reference Conditions
Wetted Material1 N/A Media: Clean, dry air/gases compatible with Aluminum, Titanium, Polybutylene Terephthalate (PBT), Buna-N®, Glass, Gold, Silicone Rubber, Silicon, Silicone - Room Temperature Vulcanizing (RTV) and Brass.

Non-Wetted Materials for Housing

N/A Stainless Steel/Lexan

Outputs

N/A 0 to 10 Vdc 0 to 5 Vdc 1 to 5 Vdc 1 to 6 Vdc 4 to 20 mA

Enclosure Ratings

N/A National Electrical Manufacturers Association (NEMA) 1

Mounting

N/A Surface Mount

Warranty

N/A 3 years

Process Connection Size

Pressure Connection Size Barbed Male

N/A 1/8 in1/4 in

Pressure Connection (National Pipe Thread (NPT) Female)

N/A 1/8 in

Pressure Connection Type

N/A National Pipe Thread (NPT) Female Barbed Male

Pressure Ranges

Pressure Ranges for Bidirectional

N/A ± 0.05 to 50.00 inH2O

Pressure Ranges for Unidirectional

N/A 0.10 to 50 inH2O

Key Features

Key Features

N/A
  • Wide selection of output signals and differential pressure ranges down to ± 0.05 in.H2O
  • Board level OEM versions available
  • Excellent overpressure protection.
  • Custom pressure range calibrations are readily available.
  • CE Mark optional

Applications

Applications

N/A Process Application:
HVAC/R
Building Energy Management
Comfort Control Systems
Fume Hood Control
Clean Room/Laboratory Pressurization
Leak Detection
Laminar Flow
Medical
Velocity Measurement
  • 1 Not for Use with Liquids