The Ashcroft® CXLdp differential pressure transmitter is designed for air handling applications including HVAC building systems, airflow metering and room pressurization control. It utilizes Ashcroft®'s SiGlas™ technology that enables unrivaled measurement sensitivity and long term repeatability. The CXLdp incorporates a host of features designed to reduce installation time and costs. It is also manufactured to Ashcroft®’s straight forward TruAccuracy™ terminal point standard that eliminates confusion from statistically derived accuracy specifications and avoids the need for user calibration at the time of installation. It is backed with a three year product warranty.
Unit of Measure

Specifications

Brands

N/A Ashcroft®

Reference Temperature

N/A 21 ºC70 ºF

Reference Temperature Tolerance (±)

N/A 2 ºF1 ºC

Accuracy

N/A ± 0.25%, ± 0.4%, ± 0.8% of Span (TruAccuracy™- Terminal Point Method: includes non-linearity, hysteresis, non-repeatability, zero offset and span setting errors)

Stability

N/A ≤ ± 0.25% span/Year at Reference Conditions

Wetted Material

N/A Media: Clean, dry air/gases compatible with Aluminum, Titanium, Polybutylene Terephthalate (PBT), Buna-N®, Glass, Gold, Silicone Rubber, Silicon, Silicone - Room Temperature Vulcanizing (RTV) and Brass.

Non-Wetted Materials for Housing

N/A Fire-Retardant Acrylonitrile Butadiene Styrene (ABS) (Meets UL 94-5VA)

Outputs

N/A 0 to 10 Vdc 0 to 5 Vdc 4 to 20 mA

Enclosure Ratings

N/A National Electrical Manufacturers Association (NEMA) 1

Mounting

N/A DIN Rail Surface Mount

Warranty

N/A 3 years

Pressure Connection

Pressure Connection (National Pipe Thread (NPT) Female)

N/A 1/8 in

Pressure Connection Size Barbed Male

N/A 1/4 in

Pressure Connection Type

N/A National Pipe Thread (NPT) Female Barbed Male

Pressure Ranges

Pressure Ranges for Bidirectional

N/A ± 0.05 to 50.00 inH2O

Pressure Ranges for Unidirectional

N/A 0.10 to 100 inH2O

Key Features

Key Features

N/A
  • TruAccuracy™ performance ensures the CXLdp meets its rated accuracy out of the box and is ready for installation with no additional calibration adjustments required.
  • LED indicator for trouble-shooting, correct wiring or locating product
  • Wide selection of differential pressure ranges
  • Euro-style pluggable terminal block; reduces wiring errors and simplifies installation
  • Field-selectable output (voltage version)
  • DIN Rail Mount is standard
  • Compact design
  • Excellent overpressure protection
  • Superior long-term stability
  • 3-Year Warranty
  • CE Mark is standard

Applications

Applications

N/A Process Applications:
HVAC/R
Critical Environments
Building/Comfort Control Systems
Fan Monitoring
Duct Flow
Fume Hood Control
Clean Room
Filter Monitoring